El NEC no dice que las bombas deban quedar conectadas a los bornes del transformador principal. Lo que especifica es que si se tiene un transformador baja - baja, no se debe poner protección en el secundario del transformador.
695.5 Transformers. Where the service or system voltage is different from the utilization voltage of the fire pump motor, transformer(s) protected by disconnecting means and overcurrent protective devices shall be permitted to be installed between the system supply and the fire pump controller in accordance with 695.5(A) and (B), or with (C). Only transformers covered in
695.5(C) shall be permitted to supply loads not directly associated with the fire pump system.
(A) Size. Where a transformer supplies an electric motor driven fire pump, it shall be rated at a minimum of 125 percent of the sum of the fire pump motor(s) and pressure maintenance pump(s) motor loads, and 100 percent of the associated fire pump accessory equipment supplied by the transformer.
(B) Overcurrent Protection. The primary overcurrent protective device(s) shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor(s) and the pressure maintenance pump motor(s) and the fullload
current of the associated fire pump accessory equipment when connected to this power supply. Secondary overcurrent protection shall not be permitted. The requirement to carry the locked-rotor currents indefinitely shall not apply to conductors or devices other than overcurrent devices in the fire pump
motor circuit(s).
695.5 Transformers. Where the service or system voltage is different from the utilization voltage of the fire pump motor, transformer(s) protected by disconnecting means and overcurrent protective devices shall be permitted to be installed between the system supply and the fire pump controller in accordance with 695.5(A) and (B), or with (C). Only transformers covered in
695.5(C) shall be permitted to supply loads not directly associated with the fire pump system.
(A) Size. Where a transformer supplies an electric motor driven fire pump, it shall be rated at a minimum of 125 percent of the sum of the fire pump motor(s) and pressure maintenance pump(s) motor loads, and 100 percent of the associated fire pump accessory equipment supplied by the transformer.
(B) Overcurrent Protection. The primary overcurrent protective device(s) shall be selected or set to carry indefinitely the sum of the locked-rotor current of the fire pump motor(s) and the pressure maintenance pump motor(s) and the fullload
current of the associated fire pump accessory equipment when connected to this power supply. Secondary overcurrent protection shall not be permitted. The requirement to carry the locked-rotor currents indefinitely shall not apply to conductors or devices other than overcurrent devices in the fire pump
motor circuit(s).
Pregunta:
ResponderBorrarSi la bomba de incendio esta alimentada de un equipo electrógeno es posible? ademas de esta misma planta se tiene conectada la carga del ascensor y otras cargas en un colegio....
Sí es posible alimentar la bomba contra incendio de un grupo electrógeno. La recomendación es que se conecte una transferencia para que el generador sólo alimente la bomba en caso de incendio. Revisar el capítulo 7, Sistemas de Emergencia.
ResponderBorrarBuena Tarde
ResponderBorrarIng Quisiera saber cual es la distancia mínima que puedo colocar una toma GFCI al lado del lavaplatos; la distancia entre el lavaplatos y la estufa son 50 cms y en este espacio también va ubicada la válvula del gas?
A mi criterio solo debes tener en cuenta que la salida eléctrica no esté a menos de 30 Cms de la salida de gas o de la válvula y que en el momento de lavar platos no le caiga agua al toma, eso creo YO
BorrarDe acuerdo con la norma, no existe una distancia mínima recomendada.
BorrarBuscando en la web veo que el ICONTEC tradujo la versión NEC 2008, ENTONCES por que no se ha actualizado la NTC 2050 si ya el ICONTEC tradujo una vesion mas actualizada?
ResponderBorrarLa versión 2008 en idioma español que circula por latinoamérica no fue avalada por el ICONTEC como oficial para Colombia, ya que fue una versión realizada para Mexico, y posteriormente para Venezuela.
BorrarBuenos días : Debo hacer corrección por ocupación en un cárcamo ? llamando cárcamo a la canalización en mamposteria regularmente que existe entre la subestcion y el TGA y q regularmente tiene tapa de alfajor Gracias
ResponderBorrarSí.... si el cárcamo está tapado, se debe considerar como una canalización cerrada....
BorrarSaludo.